EARTHING SYSTEMS
These have been designated in the IEE
Regulations using the letters: T, N, C and S.
These letters stand for:
T - terre (French for earth) and meaning a direct
connection to earth.
N - neutral
C - combined
S - separate.
When these letters are grouped, they form
the classification of a type of system.
The first letter denotes how the supply
source is earthed.
The second denotes how the metalwork of an installation is earthed. The third and fourth indicate the functions
of neutral and protective
conductors.
TT
SYSTEM
A TT system has a direct connection to the supply
source to earth and a direct connection of the installation metalwork to
earth. An example is an overhead line
supply with earth electrodes, and the mass of earth as a return path as shown
below.

Note that only single-phase systems have
been shown for simplicity.
TN-S
SYSTEM
A TN-S system has the supply source directly connected to earth, the installation
metalwork connected to the neutral of the supply source via the lead sheath of the supply cable, and the neutral and
protective conductors throughout the whole system performing separate
functions.

The resistance around the loop P-B-N-E
should be no more than 0.8 ohms.
TN-C-S
SYSTEM
A TN-C-S system is as the TN-S but the
supply cable sheath is also the neutral, i.e. it forms a combined earth/neutral
conductor known as a PEN (protective earthed neutral)
conductor.
The installation earth and neutral are
separate conductors.
This system is also known as PME (protective multiple earthing).

The resistance around the P-B-N-N loop
should be less than 0.35 ohms.
SUMMARY
OF EARTHING SYSTEMS
The TT method
is used mostly in country areas with overhead transmission lines. In contrast
to the TN-S system there is no metallic path from the consumer's terminals back
to the sub-station transformer secondary windings. Because the earth path may be of high
resistance, a residual current circuit-breaker
(R.C.C.B.) is often fitted so that if a fault current flows in the earth
path then a trip disconnects the phase supply.
For protection against indirect contact in
domestic premises, every socket outlet requires an RCCB with a maximum rated
current of 30mA.
The TN-S system of wiring uses the incoming cable
sheath as the earth return path and the phase and neutral have separate
conductors. The neutral is then
connected to earth back at the transformer sub-station.
Remember in TN-S, the T stands for earth
(terre), N for neutral and S denotes that the protective (earth) and neutral
conductors are separate.
The TN-C-S
system has only two conductors in the incoming cable, one phase and the other
neutral. The earth is linked to the
neutral at the consumer unit. The
neutral therefore is really a combined earth/neutral conductor hence the name PME.
In order to avoid the risk of serious
electric shock, it is important to provide a path for earth leakage currents to
operate the circuit protection, and to endeavour to maintain all metalwork at
the same potential. This is achieved by bonding together all metalwork of electrical and
non-electrical systems to earth.
The path for leakage currents would then be
via the earth itself in TT systems or by a metallic return path in TN-S or
TN-C-S systems.
NOTES
Older houses in towns use
TNS (solid) i.e. separate earth say
cable sheath.
Around Towns new houses use
(PME) TNCS i.e. neutral and earth shared.
Single House in country with
own transformer uses TT i.e. own buried earth electrode.
Petrol stations, Swimming
pools, Changing rooms etc. are not allowed to be PME.