Elements
of Controls - Sensors - Page 1 2 3 4 5 6 7 8 9 10 ![]()
Sensors
The sensor or
detecting element of a control system sends a signal to the comparison device.
This is a
negative feedback signal that is compared with the Desired
value or Set point.
The comparison
device compares the feedback signal from the sensor with the set point setting
and works out the difference between them – this is the error signal.
The error
signal is then fed to the controller.

The siting of sensors is critical to achieve good
control.
In pipework
or ductwork, sensors must be arranged so that the active part of the device is
immersed fully in the fluid and that the position senses the average condition.
Sometimes averaging devices
are used to give an average reading of measured variable e.g. an averaging stat
measuring temperature.
In sensing
space conditions, the sensing device must not be in the path of direct solar radiation or be located on a surface which
would give a false reading such as a poorly insulated external wall.
Local effects
from heat sources, radiators or office
equipment for example will also give unsatisfactory results and in the case of
temperature sensors give higher measurements than the true values.
Temperature Sensors
Thermal
expansion of metal or gas and a change in electrical characteristics due to
temperature variation are common methods of detection.

Bi-Metallic Strip
The figure
below shows a simple bi-metallic type thermostat
with closing point contacts.

Sealed
Bellows
The sealed
bellows type is filled with a gas, vapour or liquid, which responds to change
in temperature by variation in volume and pressure causing expansion or contraction.

Bulb & Capillary Sensor
Bulb and
capillary elements are used where temperatures are to be measured in ducts,
pipes, tanks or similar locations remote from the controller.
The bulb is
filled with liquid, gas or refrigerant depending on the temperature range
required.
Expansion
of
the fluid in the heated bulb exerts a pressure which is transmitted by the capillary to the diaphragm and there translated
into movement.

Electrical /
Electronic Sensors
It is common
to measure temperature, pressure or flow and convert these parameters to electrical signals, especially in building energy
management systems (BEMS).
This measurement and conversion
to an electrical signal is the function of the sensor, transmitter and
transducer.
The sensor
responds to a change in a measured parameter,
the transducer changes the sensor signal to an electrical
signal (e.g. a pressure into a voltage) and the transmitter is the
electronic circuitry to enable a suitable strength voltage
proportional to the sensed parameter to be sent to a controller or BEMS
outstation.
Electronic
sensors
have no moving parts.
The
resistance bulb type, normally a coil of nickel, copper or platinum wire around
a core, produces a variation in electrical resistance
with change in temperature.
Thermistors,
which are semi-conductor devices, also produce a change in resistance so that
resistance decreases with increase in temperature.
Thermocouples
have two dissimilar metal wires joined at
one end.
The output is
a voltage proportional to the temperature difference between the junction and
the free ends.
Dead-band thermostats have been
developed to reduce energy use.
The principle
is that for comfort applications a variation in temperature of about 3oC
to 4oC is acceptable for some locations.
This type has
a wide dead-band through which a change in temperature produces no change in
the output.

Humidity
Sensors
Fabrics which
change dimension with humidity variation, such as hair, nylon or wood, are
still in use as measuring elements but are unreliable - hygroscopic plastic tape is now more common.
These media
may be used to open or close contacts or to operate a potentiometer.
For
electronic applications, use is made of a hygroscopic salt such as lithium chloride, which will provide a change in
resistance depending upon the amount of moisture absorbed. Solid state sensors
use polymer film elements to produce variations
in resistance or capacitance.

Thermoset
polymer-based capacitive RH sensors directly detect changes in “relative
saturation” as a change in sensor capacitance. Capacitive RH sensors dominate both atmospheric and process measurements and are capable of operating accurately down to 0% RH.
Thermoset polymer-based
capacitive sensors allow higher operating temperatures and provide better resistivity against chemical
liquids and vapours.
Pressure Sensors
Bellow, diaphragms and bourdon tubes are
typical sensing devices used. Bellows and diaphragms
acting against a spring are quite common devices. This equipment can be
sensitive to small changes in pressure, typically 10
Pascals.
The pressure sensing motion may then be
transmitted directly to an electric or pneumatic control device.
In electronic systems, the diaphragm or the
sensing element is connected to a solid state device which when distorted changes resistivity. This is known as the piezo-electric effect.
Flow Sensors
In water systems the most common method
used to detect fluid rate is to measure pressure difference across a
restriction to flow, such as an orifice plate or a venturi.
The Venturi meter is a device for measuring discharge in a
pipe.
It
consists of a rapidly converging section which increases the velocity of flow
and hence reduces the pressure.
It
then returns to the original dimensions of the pipe by a gently diverging
'diffuser' section.
By
measuring the pressure differences the discharge can be calculated.
This is a particularly accurate method of
flow measurement as energy losses are very small.
The diagram below shows a venturi meter,
practically the meter is incorporated into an orifice plate or regulating
valve.

Extensive
use is made of calibrated valves or regulating valves especially during
commissioning.
Various devices are available to sense air
velocity in ductwork.
The Pitot -
static tube can be used to measure total
pressure and static pressure.
The velocity can be found from the
following formula:
Total pressure = Static
pressure + Velocity pressure
Velocity pressure (V.P.) = Total
pressure - Static pressure
V.P. = 0.5 x ra x v2.
Where: V.P. = Velocity
pressure (N/m2)
ra = density of air (about 1.2 kg/m3)
v = velocity
of air (m/s)
Therefore v = ( V.P.
/ ( 0.5 x ra ) )0.5
The diagram below shows a typical
Pitot-static tube.
The tube facing the air stream is called
the facing tube and measures the total head.
The static head is obtained from the small
tappings into the annulus.
The head difference as measured in the
manometer is therefore the Velocity head. To convert from head to
pressure use the following formula:
Pressure = density of liquid in manometer x
acceleration due to gravity (9.81m/s2) x head
(meters).

In
large ducts an array of sensing devices is required to obtain an average air
velocity.

Another less accurate method of determining
air velocity is to use a hot wire anemometer.
This tends to be less accurate than using a
Pitot-static tube and is better suited to air movement measurements inside
rooms or outside.
Paddle blade switches are used in water circuits, normally as a safety
feature.
A paddle blade flow switch could be used,
for example, in a chilled water circuit connected to the evaporator of a
refrigeration plant so that the plant would not start until the switch sensed
that water flow was established.
This is to ensure that damage to equipment
is avoided if water in the evaporator freezes during a no-flow condition.
Elements
of Controls - Sensors - Page 1 2 3 4 5 6 7 8 9 10 ![]()