Design a ventilation system for the toilets in an Auditoria as shown in the accompanying drawings.
The Male Toilet and Female
Toilet should each have separate extract ventilation systems to avoid ‘cross-talk’
and spread of smoke within the ductwork system.
The mechanical ventilation
rate from Table 3.1 CIBSE
Guide B2 (2001) is at least 3 air changes per hour.
For the purposes of this
exercise use a value of 8 AC/h.

MALE TOILET
The volume of the Male
Toilet is: 4.5 x 3.0 x
2.7 m = 36.45 m3
The ventilation rate in m3/h is:
Ventilation Rate (m3/h) = Room
volume (m3) x air change rate (ac/h)
Ventilation Rate (m3/h ) = 36.45 m3 x 8 AC/h
= 291.6 m3/h. Divide by 3600
The ventilation rate is =
0.081 m3/s.
A simple method of duct sizing would be: Duct area =
volume flow rate / air velocity.
An appropriate maximum air velocity for a toilet is 4 m/s. (See Ventilation
- Ventilation Design section)
Therefore duct area = 0.081 / 4 = 0.02025
m2.
If a square duct is used then the duct size is: ( 0.02025 )0.5
= 0.142 m x 0.142 m
The nearest standard size is 0.150 m x 0.150 m or, 150mm x 150mm.
The drawing below shows the ductwork layout for the Toilets.

The flexible ductwork may be sized using the same technique as above.
Volume flow rate through each flexible = 0.081 m3/s / 2 = 0.041
m3/s.
A simple method of duct sizing would be: Duct area
= volume flow rate /
air velocity.
An appropriate air velocity for a flexible in this situation is 4 m/s
Therefore duct area = 0.041 / 4 = 0.01025
m2.
Cross sectional area = p . d2 / 4 d = (
4 . CSA / p )0.5
Therefore flexible diameter = ( 4
x 0.01025 / p )0.5 = 0.114 m = 114 mm diameter.
The nearest standard size of PVC flexible is 125mm.
The flexible size should be smaller than the duct to which it is attached
to enable a boot or branch to be spot welded into position, as shown below.

The Female Toilet may be sized using the same method but since the
physical dimensions are so close to the Male Toilet then the same duct sizes
can be used, this also standardizes the complete ventilation system so that the
two fans are also identical.
Fans
To choose suitable
fans for this example the duct pressure drop and fittings pressure drop would
be calculated.
If the total
pressure drop is assumed to be 200 Pa and the flow rate is 0.081 m3/s (81 litres/s) then a suitable catalogue can
be used to pick the fan.
See http://www.flaktwoods.com. Go to Other Fans section.
A tube fan or boxed
fan can be used for this project.